5 Electrical Connection SMA Solar Technology AG
14 485BRD-10-IA-en-12 Installation Manual
5.4 Preparing the Cables
Requirement:
The cable requirements are complied with (see Technical Description "RS485 Cabling Plan").
Diameter of the cable when using the cable support sleeve with one hole: at maximum 17 mm
Diameter of the cable when using the cable support sleeve with two holes: at maximum 6.5 mm
Depending on whether the inverter is located at the end or in the middle of the communication bus,
prepare one or two cables as described in the following:
1. Remove 40 mm of the cable sheath at the end of the cable to be connected to the
485 data module.
2. Shorten the cable shield to 15 mm.
3. Fold the surplus cable shield back onto the cable
sheath.
4. Wrap the cable shield with copper foil.
5. Strip the insulation on the three wires each by 6 mm. Two wires for communication must be a
twisted pair.
6. Shorten all other wires flush with the cable sheath.
Disturbance of data transmission due to AC cables
During operation, AC cables generate an electromagnetic field which may induce interference
in plant communication.
Do not lay the cables of the RS485 communication together with the AC cable.