SMA Technologie AG Technical data
Installation Guide SB700-11:SA2006 Page 39
7.5 Operating parameters
The parameters with a grey background are only visible when in installer mode.
Unauthorised changes to the operating parameters may result
in:
• Injury or accidents as a result of changing the internal
safety routines in the Sunny Boy
• Voiding the Sunny Boy's operating approval certificate
• Voiding the Sunny Boy's guarantee
Never change the parameters of your Sunny Boy without
express authorization and instructions.
Name Unit Value range Factory setting
Betriebsart /
Operating mode
MPP, IKonst, UKonst, Stopp, Turbine
Mode, Insel Mode
MPP
Default GER/ENS
dFac-Max Hz/s 0.005 ... 4.0 0.5
dZac-Max mOhm 0 ... 20000 350
E_Total kWh 0 ... 200000
Fac-Delta- Hz 0 ... 4.5 0.19
Fac-Delta+ Hz 0 ... 4.5 0.19
h_Total h 0 ... 200000
I-NiTest /
Testcurrent Zac
mA 0 ... 6000 4500/
4000/
3500
Speicherfunktion /
Memory function
Default Parameter, Reset Betriebsdaten,
Reset Fehler
none
Speicher/Storage Permanent, volatile Permanent
T-Start s 5 ... 300 10
T-Stop s 1 ... 3600 2
Uac-Min / Vac-Min V 180 ... 300 198
Uac-Max / Vac-Max V 180 ... 300 260
Upv-Start /
Vpv-Start
V 125 ... 250/
100 ... 200/
75 ... 150
150/
125/
95
Usoll-Konst /
Vconst-Setpoint
V 125 ... 330/
100 ... 330/
75 ... 330
275/
275/
275